Language
Sizes of Walk-in Temperature and Humidity Test Chamber | ||||
Model
|
Volume (m³)
|
Temperature Range
(°C) |
Internal Dimension (mm) D*W*H
|
External Dimension (mm) D*W*H
|
LRHS-8MB-LJS
|
8
|
A: -20~100°C
B: -40~100°C C: -60~100°C D: -70~100°C E: or customized |
2000*2000*2000
|
As per design drawing
|
LRHS-15MB-LJS
|
15
|
2500*3000*2000
|
||
LRHS-30MB-LJS
|
30
|
3000*5000*2000
|
||
LRHS-60MB-LJS
|
60
|
5000*6000*2000
|
||
Note: In the Model, the number means volume of test chamber's working room, and ABCD means the temperature range. For example, model LRHS-8MB-LJS means the volume of this test chamber is 8000L(8m³), and its temperature range is -40°C~+100°C. LRHS-15MC-LJS means the volume is 15000L(8m³) and the temeprature range is -60°C~+100°C |
||||
Basic Specification | ||||
Performance
|
Temperature Range | A: -20~100°C, B: -40~100°C, C: -60~100°C, D: -70~100°C, E : or customized | ||
Temperature Fluctuation | ±0.5°C(No-load) | |||
Temperature Uniformity | ≤2℃(No-load) | |||
Ramp Rate | - 40℃~100℃≤90min for heating (non-linear, based on on-load) 100℃~-40℃≤90min for cooling (non-linear, based on on-load) Note: can be customized as per requirement |
|||
Material
|
External Casing | Cold-rolled A3 (Q235) steel plates with plastics painted. | ||
Interior Working Room | Stainless Steel Plates SUS304 with miror surface | |||
Heat Isolation | Polyurethane foams and fine glass fibres | |||
Illumination Lamp | Philips® one in per standard test chamber. | |||
Viewing Window | Multi-layer hollow toughened glass with conductive films for heating to defrost | |||
Heating & Cooling System
|
Heater | Steipped Nickel-chromium Wire Heater | ||
Air Blower | Anti-temperature stainless fan blades with low noise | |||
Compressor | Hermetically-sealed Techmesh® or semi-sealed Bitzer® or GEA® or equivalent compressors | |||
Cooling Method | Single or dual cooling (Air-cooled or Water-cooled) | |||
Refrigerant | R404A or/and R23 (eco-friendly) | |||
Control System
|
Controller | 7" Programmable colorful touch-screen display LCD English Display Microcomputer integrated controller |
||
Functions | Data Record (Max 600 days x 24hrs), History Curve, USB data download & upload, Remote controlling through PC, Automatic protection alarms, etc. | |||
Temperature Sensor | Platinum Resistance.PT100Ω | |||
I/O Interface | Communicate port (RS485) to connect test chamber to a PC | |||
Standard Configuration | Test Chamber x 1,Wet Bulb Gauzex 1, φ100mm Cable Access Port x 1 with 1 soft plug, EMO x 1, Tri-color Indicator x 1, etc. | |||
Safety Protection | Power leakage protection/Compressor over-heat, over-load or over-current protection/Dry burning protection. | |||
Voltage | 380V/440V±10%, 50Hz/60Hz or as per requirement | |||
Ambient Enviromental for application | 5°C~+30°C ≤ 85%R.H | |||
Test Standards (not limited to) |
Get Price
ysl@bjyashilin.com 010-68174779Copyright © Beijing Yashilin Test Equipment Co., LTD 备案号:京ICP备08004694号
Website Map:Sitemap